Home / Sectors / Cables: CPR testing under EN 50575

Cables: CPR testing under EN 50575

Power, control and communication cables in European construction works carry Euroclasses of their own. The test chain behind classes from Fca to B2ca.

050100 HEAT FLUX kW/m²
EN 50575Product standard
EN 13501-6Classification
EN 50399Key test

Since the CPR extended to cables, a cable's Euroclass (Fca up to B2ca and beyond) is decided by fire tests: the EN 50399 bunched-cable test measures heat release (FIGRA), total heat, smoke production and flaming droplets under a hood; the single-cable flame test of EN 60332-1-2 screens ignitability; and additional smoke density (EN 61034) and acidity (EN 60754-2) measurements supply the s and a additions to the class.

The cable laboratory set

The centre is the bunched cable rig in its EN 50399 configuration, flanked by the single-cable vertical flame arrangement, the 3-metre cube for EN 61034 smoke, and, for fire-resistant cables outside the CPR reaction-to-fire logic, the IEC 60331 circuit integrity tester. The cable family page gathers the set.